Resumen

In North American, most residential electrical meters are of the form 2S type. While the neutral conductor from the split-phase transformer to the customer's service panel is routed through the meter socket, the meter does not have a connection to the neutral conductor. Line 1 and line 2 voltage magnitudes are nominally equal when referenced to the neutral. Conditions arise that the neutral connection becomes compromised, in which case the line 1 and line 2 voltages become unbalance, creating potentially hazardous conditions. This paper describe an algorithm in a form 2S smart meter can use to detect a faulted neutral connection by observing changes in the currents seen by the meter even though it does not have a direct connection to the neutral reference point. Results of laboratory experiments show that it is possible to detect faulted neutral conditions in a typical household in less than a day.

Idioma originalInglés
Título de la publicación alojada2023 IEEE PES Grid Edge Technologies Conference and Exposition, Grid Edge 2023
EditorialInstitute of Electrical and Electronics Engineers Inc.
ISBN (versión digital)9781665460125
DOI
EstadoPublicada - 2023
Publicado de forma externa
Evento2023 IEEE PES Grid Edge Technologies Conference and Exposition, Grid Edge 2023 - San Diego, Estados Unidos
Duración: 10 abr 202313 abr 2023

Serie de la publicación

Nombre2023 IEEE PES Grid Edge Technologies Conference and Exposition, Grid Edge 2023

Conferencia

Conferencia2023 IEEE PES Grid Edge Technologies Conference and Exposition, Grid Edge 2023
País/TerritorioEstados Unidos
CiudadSan Diego
Período10/04/2313/04/23