Resumen
R245fa was selected to operate with a the working fluid for a seasonal thermal energy storage (STES) heat pump whose role was to upgrade the temperature of the heat when it was insufficient to heat a hospital administration building near Warsaw, Poland. The selection of R245fa was based on a series of theoretical and laboratory tests indicating its superior performance when operating with the higher evaporator conditions encountered when working with a STES. High coefficients of performance are presented and the challenges of operating a heat pump with a STES are discussed.
| Idioma original | Inglés |
|---|---|
| Título de la publicación alojada | 24th IIR International Congress of Refrigeration, ICR 2015 |
| Editorial | International Institute of Refrigeration |
| Páginas | 3605-3612 |
| Número de páginas | 8 |
| ISBN (versión digital) | 9782362150128 |
| DOI | |
| Estado | Publicada - 2015 |
| Evento | 24th IIR International Congress of Refrigeration, ICR 2015 - Yokohama, Japón Duración: 16 ago 2015 → 22 ago 2015 |
Serie de la publicación
| Nombre | Refrigeration Science and Technology |
|---|---|
| ISSN (versión impresa) | 0151-1637 |
Conferencia
| Conferencia | 24th IIR International Congress of Refrigeration, ICR 2015 |
|---|---|
| País/Territorio | Japón |
| Ciudad | Yokohama |
| Período | 16/08/15 → 22/08/15 |
ODS de las Naciones Unidas
Este resultado contribuye a los siguientes Objetivos de Desarrollo Sostenible
-
ODS 7: Energía asequible y no contaminante
Huella
Profundice en los temas de investigación de 'High temperature heat pumps for seasonal thermal energy storage and district heating systems'. En conjunto forman una huella única.Citar esto